Experience Sharing
Solution for Chilling Power Reducing of SIC-8W Water Chillers
Problem Description
One set SIC-8W to two sets of Injection Moulding Machines (Haitian 350T and Toshiba 300T), setting temperature 22℃, actual temp. 23℃, temperature can achieve at desired level; Check the moving parameters: high pressure of refrigerant: 3.5mpa, low pressure of refrigerant: 0.56mpa, the machine works astatically.
Reason Analysis
After checking the inlet/outlet of cooling water temp., the inlet cooling water temp. 29.2℃, outlet cooling water temp. 43.2℃, the temp. difference is as high as 14℃. Cooling water supply is not enough (cooling water flow distributed from main pipe to chiller is too small). Normally, it is reasonable when temperature gap of inlet/outlet water at 5℃.
Solution
We will configure one set of pipeline pumps (flow: 90L/min) or to improve the cooling water supply pipe, which can reduce water pipe resistance and increase the volume of water suppliedt to the cooling water.
Experience Sharing
If you want to read other articles, back to2009 Quarter 4 Issue 1.